Hayward FD Heater Pressure Switch FDXLWPS1930
Water Pressure Switch Replacement Procedure.
FDXLWPS1930
for Universal H-Series (Forced-Draft) Heaters
IMPORTANT NOTES:
This kit is intended to be used only with Hayward Universal H-Series (forced-draft) gas heater models. These heaters may be
identified by inspection of the heater rating plate (there should be an "FD" in the model number), or by visual inspection of the
heater in comparison to the diagrams in these instructions.
REPLACEMENT PROCEDURE
- Turn pump, main gas valve, and heater power off.
- Remove 6 screws and remove the upper plastic heater side
panel, to allow access to the header (see Figure 1 for screw
locations).
- Disconnect wires from pressure switch.
- Remove pressure switch by un-threading it from the header
(see Figure 2 for pressure switch location).
- Install new pressure switch in header. Apply pipe thread sealant to pressure switch threads before assembly. Use care to not cross-thred the pressure switch when threading into the
header.
- Connect wires to new pressure switch.
- Test operation of the pressure switch and adjust if necessary
(see below).
- Re-install upper plastic heater side panel.
TEST / ADJUSTMENT PROCEDURE
The pressure switch is preset at the factory for most typical, deck
level installations. When the heater is located above or below the
level of the pool or spa, the pressure switch may require adjustment
to compensate for the change in static head pressure. The following
procedure is recommended when the switch needs adjustment
and/or is replaced:
For Installations with Heater Above Water Level:
- Be sure the filter is clean before making the adjustment.
- Turn "ON" the tilter pump and ensure all air is out of the water
lines, and ensure water tlow rate is 30 GPM minimum.
- Turn "ON" the heater and adjust the thermostat to create a call
for heat.
- lf the heater does not light, adjust the pressure switch by turning
the adjustment knob on the pressure switch counter-clockwise,
until the heater lights. Turning the adjustment knob counter-
clockwise decreases the pressure needed to close the switch.
- Check the function of the pressure switch by mmlng the filter
pump on and off several times. The pool heater should turn off
immediately when the pump is turned off. Never allow the heater
to operate with less than a 30 GPM water llow rate.
For Installations with Heater Below Water Level:
- Be sure the filter is clean before making the adjustment.
- Tum "0N'the ilter pump and ensure all air is out of the water lines, and ensure the water llow rate is 30 GPM minimum.
- Tum "ON" the heater and adjust the themiostat to create a call for heat F
- Turn the adjustment knob on the pressure switch clockwise, until the heater turns off, then turn the knob 1/4 turn ounter-clockwise, so that the heater turns back on. Turning the adjustment knob clockwise increases the pressure needed
to close the switch.
- Check the function of the pressure switch by turning the hlter pump on and off several times. The pool
heater should turn off immediately vmen the pump is turned off. Never alow the heater to operate with
less than a 30 GPM water llow rate.